Transformer - Hammond, Isolation / plug & receptacle
- Primary 115VAC, 50 / 60 Hz., Secondary 115VAC
- Provides complete circuit isolation.
- Electrostatic shield between primary & secondary to greatly attenuate surges and noise.
- Hi-pot tested to 2 KV RMS.
- Circuit breaker in primary.
- Standard 3-wire, grounded plug & receptacle.
- Input (primary) connected to 5 foot long cord & standard North American plug (NEMA 5-15P).
- Output (secondary) connected to 1 foot long "pig tail" cord, 3-wire, standard North American grounded receptacle (NEMA 5-15R).
- North American Mark of Safety - C UL & UL listed (File #E211544)
- Indoor use only
- Remember - These units do NOT convert line frequency
Full Load Total | Capacitance | Circuit | |||||
---|---|---|---|---|---|---|---|
Part No. | Capacity (VA) | Leakage Current | Full Load Efficienty | Harmonic Distortion | Surge/ Noise Suppression | Between Windings @ 1KHz | Breaker |
P-T171A | 100 | 72.12 µA | 89% | 0.21% | -37.7 dB | 15 pF | 1 A |
P-T171B | 200 | 47.52 µA | 93% | 0.195 % | -37.15 dB | 15 pF | 2 A |
P-T171E | 500 | 59.66 µA | 93% | 0.18% | -37.18 dB | 20 pF | 5 A |
Part No. | Dimensions | ||||
---|---|---|---|---|---|
A | B | C | D | E | |
P-T171A | 3.80 | 5.06 | 4.68 | 3.00 | 3.38 |
P-T171B | 3.80 | 5.56 | 4.68 | 3.00 | 3.88 |
P-T171E | 3.80 | 7.06 | 4.68 | 3.00 | 5.38 |
Capacity | Our Part Number | UPC/EAN | Hammond Part Number |
---|---|---|---|
100 VA | P-T171A | 623980250304 | 171A |
200 VA | P-T171B | 623980250502 | 171B |
500 VA | P-T171E | 623980250908 | 171E |
Breaker | 100 VA version | P-T171A | 1 A |
200 VA version | P-T171B | 2 A | |
500 VA version | P-T171E | 5 A | |
Capacitance Between Windings @ 1 kHz | 100 VA version | P-T171A | 15 pF |
200 VA version | P-T171B | 15 pF | |
500 VA version | P-T171E | 20 pF | |
Full Load Efficiency | 100 VA version | P-T171A | 89 % |
200 VA version | P-T171B | 93 % | |
500 VA version | P-T171E | 93 % | |
Harmonic Distortion | 100 VA version | P-T171A | 0.21 % |
200 VA version | P-T171B | 0.195 % | |
500 VA version | P-T171E | 0.18 % | |
Item Height | 4.68 in. | ||
Item Length | 3.8 in. | ||
Item Width | 100 VA version | P-T171A | 5.06 in. |
200 VA version | P-T171B | 5.56 in. | |
500 VA version | P-T171E | 7.06 in. | |
Leakage Current (IR) | 100 VA version | P-T171A | 71.12 μA |
200 VA version | P-T171B | 47.52 μA | |
500 VA version | P-T171E | 59.66 μA | |
Mounting Hole Center to Center A | 3 in. | ||
Mounting Hole Center to Center B | 100 VA version | P-T171A | 3.38 in. |
200 VA version | P-T171B | 3.88 in. | |
500 VA version | P-T171E | 5.38 in. | |
Mounting Hole Diameter | 0.20 in. | ||
Primary | 115 VAC @ 50 / 60 Hz | ||
Secondary | 115 VAC | ||
Surge/noise Suppression | 100 VA version | P-T171A | -37.7 dB |
200 VA version | P-T171B | -37.15 dB | |
500 VA version | P-T171E | -37.18 dB | |
VA Rating | 100 VA version | P-T171A | 100 |
200 VA version | P-T171B | 200 | |
500 VA version | P-T171E | 500 |
Packaging Dimensions | 100 VA version | P-T171A | 8.5 in. × 8.25 in. × 9 in. |
200 VA version | P-T171B | 7.625 in. × 7.375 in. × 5.375 in. | |
500 VA version | P-T171E | 11 in. × 7.5 in. × 7.5 in. | |
Weight (Packaging) | 100 VA version | P-T171A | 12.15 lbs. |
200 VA version | P-T171B | 14.55 lbs. | |
500 VA version | P-T171E | 24 lbs. |
P-T171A - 100 VA version | Breaker | 1 A |
Capacitance Between Windings @ 1 kHz | 15 pF | |
Full Load Efficiency | 89 % | |
Harmonic Distortion | 0.21 % | |
Item Height | 4.68 in. | |
Item Length | 3.8 in. | |
Item Width | 5.06 in. | |
Leakage Current (IR) | 71.12 μA | |
Mounting Hole Center to Center A | 3 in. | |
Mounting Hole Center to Center B | 3.38 in. | |
Mounting Hole Diameter | 0.20 in. | |
Primary | 115 VAC @ 50 / 60 Hz | |
Secondary | 115 VAC | |
Surge/noise Suppression | -37.7 dB | |
VA Rating | 100 | |
P-T171B - 200 VA version | Breaker | 2 A |
Capacitance Between Windings @ 1 kHz | 15 pF | |
Full Load Efficiency | 93 % | |
Harmonic Distortion | 0.195 % | |
Item Height | 4.68 in. | |
Item Length | 3.8 in. | |
Item Width | 5.56 in. | |
Leakage Current (IR) | 47.52 μA | |
Mounting Hole Center to Center A | 3 in. | |
Mounting Hole Center to Center B | 3.88 in. | |
Mounting Hole Diameter | 0.20 in. | |
Primary | 115 VAC @ 50 / 60 Hz | |
Secondary | 115 VAC | |
Surge/noise Suppression | -37.15 dB | |
VA Rating | 200 | |
P-T171E - 500 VA version | Breaker | 5 A |
Capacitance Between Windings @ 1 kHz | 20 pF | |
Full Load Efficiency | 93 % | |
Harmonic Distortion | 0.18 % | |
Item Height | 4.68 in. | |
Item Length | 3.8 in. | |
Item Width | 7.06 in. | |
Leakage Current (IR) | 59.66 μA | |
Mounting Hole Center to Center A | 3 in. | |
Mounting Hole Center to Center B | 5.38 in. | |
Mounting Hole Diameter | 0.20 in. | |
Primary | 115 VAC @ 50 / 60 Hz | |
Secondary | 115 VAC | |
Surge/noise Suppression | -37.18 dB | |
VA Rating | 500 |
Specification Sheet for 100 VA | P-T171A |
Specification Sheet for 200 VA | P-T171B |
Specification Sheet for 500 VA | P-T171E |
Circuit Drawing | All Models |
My Project Lists
Questions? Contact us at [email protected], or give us a call at 480-820-5411
Product Reviews
Great product with fast shipping. Very pleased with the purchase and will buy again!!!
This transformer is a HUNK! It is so well built and, well, heavy ... the unit is well coated for long-term use on the bench, its heavy gage wiring and should handle the rated amperage quite well. I'm very well pleased with it and I am convinced it will be very useful for much longer than I'll be around ...